Project | Units | C Module | F Module | V Module | CB Module | ||
Load Switch | Combination Electric Appliance | Vacuum Switch | Isolation/Grounding Switch | Vacuum Circuit Breaker | Isolation/Grounding Switch | ||
The Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated Frequency | HZ | 50 | 50 | 50 | 50 | 50 | 50 |
Power Frequency Withstand Voltage (Phase/Fracture) | KV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48a |
Lightning Shock Withstand Voltage | KV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | infuse1) | 630 | 1250/630 | ||
Breaking Ability: | |||||||
Rated Closed Loop Breaking Current | A | 630 | |||||
Rated Cable Charging Break Current | A | 10 | |||||
Rated Short Circuit Closing Current (Peak) | A | 50 | 80 | ||||
Rated Peak Tolerable Current | kA | 50 | |||||
Rated Short-Time Tolerable Current | kA/35 | 20 | |||||
Rated Short Circuit Breaking Current | kA | 31.5 | 20 | 25 | |||
Rated Transfer Current | A | 1700 | |||||
Use The Maximum Current Of The Fuse | A | - | 125 | ||||
Loop Resistance | -n | ≤300 | ≤600 | ||||
Mechanical Life | next | 5000 | 3000 | 5000 | 2000 | 5000 | 2000 |
Note: Depends On Current Rating Of The Fuse | |||||||